weiter zur Liste zurück pdf print Heavy duty connector C 146 HvE
![]() | 660 V, 16 / 22 A - |
![]() | 600 V, 10 A E 63093 |
![]() | 600 V, 20 A 48932 |
| In general approvals refer to representative versions of the connector. Extent and specification of tests upon request | |
Connectors C 146 HvE Male insert No. of contacts 3 + PE + 2, 660 V, Termination: screw, Contact plating: silver plated, 2 delayed mating contacts | ||
| Part No. | C146 10A003 102 3 | |
| Series | Heavy duty connectors C 146 | |
| Subseries | Heavy duty connector C 146 HvE | |
| Common Characteristics | ||
| No. of contacts | 3 + PE + 2 | |
| Weight male insert | 49 g | |
| Weight female insert | 49 g | |
| Electrical Characteristics | ||
| Rated voltage | DIN EN 60664-1 / IEC 60664-1 | 660 V (600 V UL / CSA) |
| Rated impulse voltage | DIN EN 60664-1 / IEC 60664-1 | 8000V |
| Voltage proof | DIN EN 60512-2, Test 4a / IEC 60512-2, Test 4a | 3.500 V |
| Installation category | DIN EN 60664-1 / IEC 60664-1 | ||| |
| Insulation group | DIN EN 60664-1 / IEC 60664-1 | III a / II |
| Insulation resistance | DIN EN 60512-2, Test 3a / IEC 60512-2, Test 3a | ≥ 1012 Ω |
| Contact resistance | DIN EN 60512-2, Test 2a / IEC 60512-2 Test 2a | < 5 mΩ |
| Current carrying capacity | DIN EN 60512-3, Test 5b / IEC 60512-2 Test 5b | see derating curves |
| Pollution degree | DIN EN 60664-1 / IEC 60664-1 | 3 |
| Climatical Characteristics | ||
| Climatic category | DIN EN 60068-1 / IEC 60068-1 | 40 / 125 / 21 |
| Upper temperature | + 125 °C / 1000h | |
| Lower temperatur | - 40 °C / 16h | |
| Mechanical Characteristics | ||
| IP degree of protection | DIN EN 60529 / IEC 60529 | IP00 unmated |
| Mechanical lifetime | IEC 60512-5; Test 9 a | ≥ 500 mating cycles |
| Materials | ||
| Contacts | CuZn | |
| Colour | grey | |
| Contact plating | silver plated | |
| Further Characteristics | ||
| Termination | screw | |
| Wire gauge | 0,25 - 2,5 mm² | |
| Flammability | UL 94 | V-0 |